ECL

ECL Emergency Exit Combo

Ideal for commercial where economy, appearance and the ultimate ease of installation and maintenance are desired. A combination exit and emergency incandescent lighting unit in one clean, low-profile modern design. Standard with two fully adjustable, glare-free incandescent emergency lighting heads.

American Recovery And Reinvestment Act Logo vandal resistant certification logo UL Certification Logo
Inventory and Lead Time

Contact us for availability and pricing information.

Need assistance?
Call us at (866) 471-7711

Downloads & Resources

Spec Sheet

Complete product specifications and technical details

Accessories

List and specification of accessories related to a product

Product Overview

Ideal for commercial where economy, appearance and the ultimate ease of installation and maintenance are desired. A combination exit and emergency incandescent lighting unit in one clean, low-profile modern design. Standard with two fully adjustable, glare-free incandescent emergency lighting heads.

Feature:

- Thermoplastic LED Exit Sign Compact size low-profile design LED exit sign.
- Innovative, snap-together design allows for fast and easy installation. Two fully adjustable glare-free square shape light heads for emergency light.
- Letters 6” height with 3/4” stroke.
- Easily removable snap-out knockouts and chevron directional arrows.
- Single or double face configuration.
- 90+ minute emergency operation.
- Available in white or black housing.
- Bug eyes are adjustable vertically.

 

Mounting:

- Universal (wall or ceiling) mounting. 
- Universal knockouts on back plate allow for wall mounting directly to standard J-Box. 
- Canopy and mounting hardware provided.

 

Lamp:

- Emergency light for 2 pcs x 6V 5.4 watts DC T5 wedge base lamps for emergency mode.
- Exit for 3.8 watts at normal operation, 15 watts at emergency operation.
- LEDs mounted on print circuit board. 
- LED lamps are operating in normal (AC input) and emergency (DC input) modes.

 

Electrical:

- 120/277V dual voltage operation standard.
- Charge rate and power “ON” LED indicator light and push-to-test switch for mandated code compliance testing.

 

Battery:

- Maintenance-free and 6V 4.5Ah rechargeable Lead-Calcium battery on emergency (EM) units.
- Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. Internal solid-state transfer switch automatically connects the internal battery to LEDs for minimum 90 minute emergency illumination.
- LVD (Low Voltage Disconnection) prevents battery from deep discharge.

 

Listing:
- 5 years limited warranty on materials and all electronics.
- LED lamps are 25 years limited warranty. 
- UL listed for damp locations & meets UL924, National Electrical Code, NFPA 70 and the Life Safety Code, NFPA 101.

Specifications

Ordering Information
  • BAA, BABA or ARRA Compliant: ARRA only